GDJB-PC Universal Three Phase Relay Protection Tester Secondary Current Injection Test Set

Product Description

GDJB-PC 

Universal Three Phase Relay Protection Tester Secondary Current Injection Test Set

(Industrial Computer Control Version)



1. Introduction


  • GDJB-PC Universal Three Phase Secondary Current Injection Test Set is applied to test the relay unit in relay protection system. At the same time it could be considered as a universal three phase AC/DC voltage source or current source.

  • GDJB-PC Universal Three Phase Relay Protection Tester Secondary Current Injection Test Set is applied to test protection replay based on voltage and current operation.

  • The main function of the tester include: calibration of voltage and current operation relays, secondary circuit inspection,trip value of circuit breaker test, switch on and off time measurement of circuit breaker and so on.

  • The standard output of 4 phases of voltage and 3 phases of current.  

  • It could combine various type of current or voltage conveniently and has diversity type of protective experiment. Every phase of voltage output is 120V, and the total of the parallel current is 120A. The fourth phase voltage Ux has many functions and it can be set to be 4 type of every three voltages or synchronism checking voltage, or output any value of voltage.

  • Equipped with ultra-thin industrial keyboard and photoelectric mouse, it can complete all kinds of operations through keyboard or mouse just like ordinary PC.

  • Equipped with independent dedicated DC auxiliary voltage source output, the output voltage is 110V (1a), 220V (0.6A).It can be used for relays or protection devices that need DC power supply.

  • It’s a low cost, simple operation and reliable performance device for secondary circuit test.



2. Specifications


AC Current Source (3 * 40A)
Single phase current output (RMS) 0-40A / phase, accuracy: 0.2% ± 5mA
Three phase parallel output (RMS) 0- 120A / three phase in phase parallel output

Allowable working value of phase current for a long time (effective value)

10A

Maximum output power per phase

400VA

Maximum output power of three phase parallel current

1000VA

Maximum output allowable working time of triple parallel current

10s
Frequency range

0 - 1000Hz, accuracy 0.01Hz

Harmonic number

2-20second

Phase

0-360 The accuracy is 0.1 degree

DC current source

DC current output

0--± 10A / phase, accuracy: 0.2% ± 5mA


AC voltage source

Single phase voltage output (RMS)

0 -125V / phase, accuracy: 0.2% ± 5mv

Line voltage output (RMS)

0-250V

Phase voltage / line voltage output power

75VA/100VA

Frequency range

0-1000Hz, accuracy: 0.001Hz

Harmonic number

2-20second

Phase

0-360Degree, accuracy: 0.1 degree

DC voltage source


Single phase voltage output amplitude

0-± 150V, accuracy: 0.2% ± 5mv

Output amplitude of line voltage

0-±300V

Phase voltage / line voltage output power

90VA/180VA


Switching value terminal

Switch input terminal

8

Air contact

1-20 mA, 24 V, internal active output of the device

Potential reversal

Passive contact: low resistance short circuit signal

Active contact: 0-250V DC

Switch output terminal

4, no contact, breaking capacity: 110V / 2A, 220V / 1A


Others


Time frame

1ms-9999s, measuring accuracy: 1ms

Power Supply

AC220V±10%,50Hz/60Hz


3. Hardware Composition of the GDJB-PC Three Phase Secondary Current Injection Test Set (Industrial Computer Control Version)


  • Built in high performance industrial control computer

  • DSP digital signal processing system

  • D/A and a/D conversion

  • High precision linear voltage and current power amplifier

  • Switch input and switch output