GDRZ-903 Transformer Sweep Frequency Response Analyzer (SFRA and Low-voltage Short-circuit Impedance)

Product Description

GDRZ-903 

Transformer Sweep Frequency Response Analyzer



Functions


  • Two test methods: Sweep Frequency Response Analysis Method and Low-voltage Short-circuit Impedance Method.

  • Follow two international test standards: IEC60076-18-2012 and IEC60076-5-2006

  • Using the advanced technical of DDS;

  • Using the high speed and advanced microprocessor to design;

  • Using AD chip of 16 bits;

  • With seven inch LCD touch screen of which the brightness can be adjusted;

  • With thermal printer of which the print thick can be adjusted;

  • It could store one hundred and twenty groups of FRA data, fifty groups of SCI data and thirty groups of SCI data, which could be read to current screen or upload to the PC;

  • With PC software using which we could upload data ,test, analyze data, print data, or create word document;

  • Using USB2.0 to connect to the device


Specifications


Sweep Frequency Response Method

Two different sweep modes
1

Linear sweep

10HZ-1MHZ,interval 0.5KHZ, 2000 dots;

100HZ-2MHZ,interval 0.5KHZ,    2000 dots;

10HZ-1MHZ, interval 0.25KHZ,   4000 dots (PC available)

100KHZ-2MHZ,      interval 0.25KHZ,   4000 dots(PC available)

Frequency, interval, and scan dots can be set(PC available)

2

Section sweep

10HZ-100HZ,         interval  1HZ,      90 dots;

100HZ-1KHZ ,interval  5HZ ,180 dots

1KHZ -10KHZ ,interval  50HZ,     180 dots

10KHZ-100KHZ, interval  0.2KHZ ,450 dots

100KHZ –300KHZ ,interval  0.5KHZ ,400 dots

300KHZ – 1000KHZ ,interval  1KHZ ,700 dots

3

Test range

(-100dB) - (+20dB)

4

Test accuracy

(-80dB) - (+20dB) 0.2dB  (-100dB) - (-80dB) 1.0dB

5

Frequency accuracy

< 0.01%

6

Signal input impedance

> 1M Ω

7

Signal output impedance

50 Ω

8

In-phase test repetition rate

99.5%

Short-circuit Impedance and Generator Rotor AC Impedance

1

AC impedance

0-999.999Ω 0.2%±2 digits

2

AC voltage

0-600V 0.2%±2 digits

3

AC ampere

0-120A 0.2%±2 digits

4

Active power

cosφ>0.1  0.5%±2 digits

cosφ<0.1  1.0%±2 digits

5

Reactive power

0.2%±2 digits

6

Frequency

45~65HZ 0.1%


Accessories





Our Partners



Contact Us


Contact Person: Christine Gou

Whatsapp/Wechat: +86 15123029885

Mobile: +86 15123029885

E-mail: gold05@hy-industry.com