GDYJ-505H 80KV 100KV Transformer Oil Dielectric Breakdown Voltage Tester Insulating Oil BDV Tester

Product Description

GDYJ-505H 80KV 100KV Transformer Oil Dielectric Breakdown Voltage Tester Insulating Oil BDV Tester





The importance of using GDYJ-505H Oil Dielectric Breakdown Voltage Tester to test transformer oil:


The breakdown voltage of transformer oil is an important indicator for measuring the degree of contamination of transformer oil by water and suspended impurities. If the breakdown voltage of transformer oil is lower, the overall insulation performance of the transformer will be worse. It will directly affect the safe operation of the transformer. Therefore, it is necessary to use a transformer oil breakdown voltage tester for strict testing and control the transformer oil breakdown voltage within different ranges.


GDYJ-505H follows the following testing standards:


IEC60156/IS6792/BS5874: Insulating liquids - Determination of the breakdown voltage at power frequency - Test method

ASTM D877: Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes

ASTM D1816: Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using VDE Electrodes


Operation screen of GDYJ-505H

IEC 60156

ASTM D1816

ASTM D877

Introduction


  • GDYJ-505H Transformer Oil Dielectric Breakdown Voltage Tester is an upgraded version of model GDYJ-502A. The functional indicators can be fully covered. The circuit board and IC have been completely replaced with the latest IC and board. 

  • The test standards are IEC60156, IS6792, BS5874, ASTM D1816 and ASTM D877.

  • The max output voltage is 80kv(100kv as optional).

  • Compact design. The weight is 10KG lighter than GDYJ-502A.


Main Test Functions of GDYJ-505H Transformer Oil Dielectric Breakdown Voltage Tester:


1) IEC60156/IS6792/BS5874

2) ASTMD877

3) ASTMD1816

4) User-defined

5) 5 minute test

6)JIS C 2101-99(S)

7) Proof ‘A’

8)Proof ‘B’


Technical Index


1

Output voltage

0-80kV(0-100kV Optional)
2

Rate of voltage rise

0.5kv/s± 5%, 2kv/s± 5%, 3kv/s± 5%, 5kv/s± 5%

3

Test Standards

IEC60156/IS6792/BS5874, ASTM D1816 , ASTM D877

4

Max. test times

9
5

Init wait times

0-999s
6

Stir time

0-99s
7

Wait time

0~600s

8

Measurement accuracy

±(1% of full scale + 2 digits)

9 Resolution 0.1KV
10 Oil Temperature measurement range

0°C to 70°C, or better.

Resolution: 1°C, or better

11 Power supply AC220V±%, 50Hz/60Hz


Our Partners


Contact Us


Contact Person: Christine Gou

Whatsapp/Wechat: +86 15123029885

Mobile: +86 15123029885

E-mail: gold05@hy-industry.com


Product Inquiry

GDYJ-502A Touch Screen 100kV Transformer Oil Dielectric Breakdown Voltage BDV Tester ASTM D1816

GDYJ-502 Hot Sale 100kV Transformer Insulating Oil Dielectric Strength Tester

GDYJ-502A IEC156 Automatic 80kV Transformer Oil Breakdown Voltage BDV Tester