Call us!

Mobile/Whatsapp/Wechat:
+86 15123029885

Write to us!

Home » Products » Transformer Tester » Tan Delta Tester » 10kV Transformer Dielectric Loss Tester

loading

Share to:
sharethis sharing button

10kV Transformer Dielectric Loss Tester

Transformer dielectric loss tester is a high-accuracy testing instrument used to test the dielectric loss tangent and capacitance of various high-voltage power equipment on-site or in laboratories such as power plants, substations, and transformer factories.
By using digital notch technology, the interference of power frequency electric fields on testing can be avoided, fundamentally solving the problem of accurate measurement under strong electric field interference. Meanwhile, It’s suitable for situations where a generator is used for power supply testing after a complete power outage.
Availability:
Quantity:
  • GDGS

  • CHONGQING GOLD

  • 9031809090

10kV Transformer Dielectric Loss Tester


Transformer Dielectric Loss Tester


Transformer Dielectric Loss Tester (2)



Why is it necessary to conduct dielectric loss testing on transformers?


The purpose of transformer dielectric loss test is to test the insulation performance of transformers. By measuring the dielectric loss factor tg δ value, the insulation status of transformer oil can be determined to ensure the safe operation of transformers.

Dielectric loss factor tg δ value: For transformers of different voltage levels, there are different standards for the dielectric loss factor tg δ value. For example, when the voltage level of the transformer is 330KV, the dielectric loss factor tg δ value should be ≤ 0.040; When the voltage level of the transformer is ≥ 500KV, the dielectric loss factor tg δ value should be ≤ 0.020.



Main Functions

  • Large touch screen, easy to operate.

  • The Transformer dielectric loss tester can be tested using various methods such as internal high voltage, external high voltage, internal standard, external standard, positive connection method, reverse connection method, self-excited method, etc; Under the external standard external high-voltage positive connection method, high voltage (greater than 10kV) dielectric loss can be achieved.

  • The Transformer dielectric loss tester can accurately measure the dielectric loss and capacitance values of the CVT without removing the high voltage leads of the CVT.

  • The Transformer dielectric loss tester can use reverse shielding method to measure the dielectric loss value and capacitance value of C0 at the upper end of CVT.

  • This instrument can also test the dielectric loss and capacitance of fully sealed CVT (capacitive voltage transformer) C1 and C2, achieving simultaneous testing of C1 and C2. This instrument can also test CVT ratio and voltage angle error.


Technical Index


1 Anti interference principle frequency conversion method
2 Power Supply 220V±10%. (AC127V and AC110V can be customized)
3 High output Voltage output: 0.5KV-10KV,Every 0.1kV
Precision: 2%
Maximum current: 200mA
Capacity:2000VA
4 Self-excited power

AC 0V∽50V/15A.


45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

5 Resolving power

tgδ: 0.001%

Cx: 0.001pF

6 Precision

△tgδ:±(Reading*1.0%+0.040%).

△C x :±(Reading*1.0%+1.00PF).

7 Measuring range tgδ:Unlimited

Cx: 15pF< Cx <300nF

10KV: Cx < 60  nF

5kV: Cx < 150 nF

1kV:Cx < 300 nF

CVT test: Cx < 300 nF
8 CVT range 10-10000
9 Accuracy 0.1%


Our Partners


Partners


Contact Us


Contact Person: Christine Gou

Whatsapp/Wechat: +86 15123029885

Mobile: +86 15123029885

E-mail: gold05@hy-industry.com

Skype: christinejinhua@outlook.com


Previous: 
Next: 
Product Inquiry

QUICK LINK

PRODUCT LIST

CONTACT US

Phone : +86 15123029885
Add : Technical Central Building,Eco &Tech Dep Zone, Nan'an District, Chongqing,China
E-mail : gold05@hy-industry.com
Fax : 0086-23-62940030
Whatsapp : +8615123029885
Wechat : + 8615123029885
Copyright  Chongqing Gold Mechanical&Electrical Equipment Co.,Ltd. All rights reserved. Site Map
公安备案号 50010802002590